30/30

  • Water resistant cardboard frame
  • Robust construction.
  • Bonded cross members to maintain pleat spacing
  • Fully supported media bonded onto a wire support grid
  • Radial pleat design for full media utilization
  • Replaceable filter media
  • ICON7 iso16890.ai
  • ICON42 UL logo
  • ICON51 MyHIJAU_Malaysia.ai
  • ICON23 Eurovent_no_abc
ISO 16890 Filter Class EN779 Width (mm) Height (mm) Depth (mm) Airflow (m3/h) Pressure drop Initial (Pa) Energy (kWh/year) Energy Class (Eurovent)
ePM10 50% G4 594 594 22 2380 60 >1100 E
ePM10 50% G4 495 594 22 1980 60 E
ePM10 50% G4 495 495 22 1650 60 E
ePM10 50% G4 495 622 22 2065 60 E
ePM10 50% G4 394 495 22 1326 60 E
ePM10 50% G4 394 622 22 1650 60 E
ePM10 50% G4 292 594 22 1190 60 E
ePM10 50% G4 594 594 44 3400 70 >1100 E
ePM10 50% G4 495 495 44 2363 70 E
ePM10 50% G4 495 622 44 2958 70 E
ePM10 50% G4 495 594 44 2839 70 E
ePM10 50% G4 444 594 44 2550 70 E
ePM10 50% G4 394 622 44 2363 70 E
ePM10 50% G4 394 495 44 1870 70 E
ePM10 50% G4 394 594 44 2270 70 E
ePM10 50% G4 343 495 44 1658 70 E
ePM10 50% G4 289 594 44 1700 70 E
ePM10 50% G4 619 619 95 3689 65 D
ePM10 50% G4 594 594 95 3400 65 1098 D
ePM10 50% G4 492 619 95 2958 65 D
ePM10 50% G4 492 594 95 2839 65 D
ePM10 50% G4 492 492 95 2363 65 D
ePM10 50% G4 390 619 95 2363 65 D
ePM10 50% G4 390 492 95 1870 65 D
ePM10 50% G4 289 594 95 1700 65 D

Specifications

Application
Prevention of dust and dirt build up on heating/cooling coils within ventilation systems
Filter Frame
Cardboard
Media
Synthetic
Max temperature (°C)
70ºC maximum in continuous service
Recommended final pressure drop
250 Pa
Max final pressure drop, EN 13053
Initial pressure drop + 50 Pa or initial pressure drop x3 (whichever is lower)
Installation options
Front and side access housings and frames are available, Type 8 and FC Housings
Comment
Fire rating: UL 900